10A Single Zone Vent Interface Unit

The single zone vent interface is the most simple and user friendly solution on the market today. The unit is loop controlled and provides direct control of reversing polarity vents or 3 wire (drive open and drive closed vents)

The unit is provided (in standard format) with a 10.25A power supply unit with space for 17Ah batteries.

The vent interface units are wired to the same 2 core detection loop as the detectors, interfaces and fireman’s keyswitch units.

A radial circuit runs between the vent interface unit and the vent or damper.

Monitoring

The Vent Interface monitors the status of the EN 54-4 certified power supply unit for all required fault conditions. Cabling to the vent or damper is fully monitored for open and short circuits. All fault conditions are repeated at the control and indicating equipment.

Flexibility

By utilising the control panels powerful cause and effect programming the vent interface unit can also provide full environmental control of dampers and vents with fully adjustable opening times for different modes.

If required damper open and close status can be monitored and these signals repeated at custom mimic indicator panels (if required)

Customisable

Vent Interface Units can be provided to control separate environmental dampers. Multi zone units are available to provide a centralised wiring location.

Specification
Mains Supply Voltage 230V
Mains Supply Fuse 20mm 3A Slow Blow
Load Output Voltage 19-30V +/- 1%
Maximum Load Current 10.25A Continuous with maximum battery charge output of 1.25A
Load Fuse 10.25A Self Resetting
Maximum Battery Load 10 Amp
Battery Charge Output Voltage 27.4V DC nominal at 20 degrees C (temperature compensated from -5 - +45 degrees C)
Operating Temperature -5 to +45 degrees C
Dimensions Dimensions 500mm (w) x 460mm (h) x 190mm (d)
Battery Disconnected Monitoring Yes
Battery Low Fault Monitoring Yes
Charger Fault Monitoring Yes
Earth Fault Monitoring Yes
Mains Failure Monitoring Yes
Damper Cable Monitoring Yes
Wiring Wiring 2 Core Loop Wiring
Enclosure / Colour Steel IP30 / BS 00 A 05 Grey Fine Texture Powder Coat
Metalwork Options Flushing bezel, battery box, utility enclosure, termination enclosure and rack mount
Approvals EN 54-4:1998 & EN 54-17 & 18
Specification

Mains Supply Voltage

230V

Mains Supply Fuse

20mm 3A Slow Blow

Load Output Voltage

19-30V +/- 1%

Maximum Load Current

10.25A Continuous with maximum battery charge output of 1.25A

Load Fuse

10.25A Self Resetting

Maximum Battery Load

10 Amp

Battery Charge Output Voltage

27.4V DC nominal at 20 degrees C (temperature compensated from -5 - +45 degrees C)

Operating Temperature

-5 to +45 degrees C

Dimensions

Dimensions 500mm (w) x 460mm (h) x 190mm (d)

Battery Disconnected Monitoring

Yes

Battery Low Fault Monitoring

Yes

Charger Fault Monitoring

Yes

Earth Fault Monitoring

Yes

Mains Failure Monitoring

Yes

Damper Cable Monitoring

Yes

Wiring

Wiring 2 Core Loop Wiring

Enclosure / Colour

Steel IP30 / BS 00 A 05 Grey Fine Texture Powder Coat

Metalwork Options

Flushing bezel, battery box, utility enclosure, termination enclosure and rack mount

Approvals

EN 54-4:1998 & EN 54-17 & 18

Follow us for the
latest news, updates
and discussions